Some Guidelines in Flowmeter Selection for Liquids
Some Guidelines in Flowmeter Selection for Liquids | ||||||
Flowmeter element | Recommended Service | Rangeability | Pressure Loss? | Typical Accuracy, percent | Required Upstream pipe, diameters | Effects from changing viscosity? |
Coriolis mass Meter | Clean dirty viscous liquids some slurries | 10 to 1 | Low | ±0.5 of rate | None | None |
Elbow meter | Clean dirty liquids some slurries | 2.5 to 1 | Very low | ±5 to ±10 of full scale | 30 | Low |
Electromagnetic | Clean, dirty viscous con- ductive liquids and slurries | 40 to 1 | None | ±0.5 of rate | 5 | None |
Flow nozzle | Clean and dirty liquids | 4 to 1 | Medium | ±1 to ±2 of full scale | 10 to 30 | High |
Orifice | Clean, dirty liquids; some slurries | 4 to 1 | Some | ±2 to ±4 of full scale | 10 to 20 | High |
Pitot tube | Clean liquids | 3 to 1 | Very low | ±3 to ±5 of full scale | 20 to 30 | Low |
Positive Displacement | Clean viscous liquids | 10 to 1 | High | ±0.5 of rate | None | High |
Target meter | Clean dirty viscous liquids some slurries | 8 to 1 | Medium | ±1 to ±5 of full scale | 10 to 28 | Medium |
Thermal Mass | Clean dirty viscous liquids some slurries | 10 to 1 | Low | ±1 of full scale | None | None |
Turbine | Clean, viscous liquids | 20 to 1 | High | ±0.25 of rate | 5 to 10 | High |
Ultrasonic (Doppler) | Dirty, viscous liquids and slurries | 10 to 1 | None | ±5 of full scale | 5 to 30 | None |
Ultrasonic (Transit Time) | Clean, viscous liquids some dirty liquids(depending on brand) | 40 to 1 | None | ±1 to 3 of full scale | 10 | None |
Variable area | Clean dirty viscous liquids | 10 to 1 | Medium | ±1 to ±10 of full scale | None | Medium |
Venturi | Some slurrys but clean dirty and liquids with high viscosity | 4 to 1 | A little | ±1 of full scale | 5 to 18 | High |
Vortex | CLean, dirty liquids | 10 to 1 | Medium | ±1 of rate | 10 to 20 | Medium |
Wedge | Slurries and liquids with high viscosity | 4 to 1 | A little | ±0.5 to ±2 of full scale | 10 to 30 | Low |
Weir V-notch | Clean, dirty liquids | 100 to 1 | Very low | ±2 to ±5 of full scale | None | Very Low |